Unit 3 — Refrigeration System Fundamentals & Maintenance
Section 2 — Phase Transition of Water

2.4 Pressure, Boiling Point & Refrigerant Behaviour

The boiling point of any liquid changes with pressure. This single fact is the entire basis of mechanical refrigeration — by controlling pressure, a technician controls where and at what temperature a refrigerant boils and condenses.

Jump to section

📊Pressure & Boiling Point 🧪Refrigerant Boiling Points 🔺Superheat 🔻Subcooling

2.4.1 — Pressure Controls Boiling Point

Water boils at 212°F (100°C) at sea level because that is atmospheric pressure. At the top of a mountain where pressure is lower, water boils at a lower temperature — about 194°F (90°C) at 10,000 ft. In a pressure cooker where pressure is higher, water boils above 250°F (121°C). The liquid is the same; only the pressure changes.

📊

The Rule: Higher Pressure = Higher Boiling Point

Increase Pressure
  • Boiling point rises
  • Liquid stays liquid at higher temperatures
  • More energy needed to boil
  • Used in condensers
Decrease Pressure
  • Boiling point falls
  • Liquid boils at lower temperatures
  • Less energy needed to boil
  • Used in evaporators
📌
The Key Insight

A refrigeration system is essentially a pressure management system. The compressor creates high pressure on one side (condenser) and low pressure on the other (evaporator). These two pressures set the two temperatures at which the refrigerant changes state — and those temperatures determine what the system can heat or cool.

💡

Example — R-134a in a Car Air Conditioner

R-134a has a boiling point of −15°F (−26°C) at atmospheric pressure. In a car AC system:

Location Pressure Saturation Temp. What Happens
Evaporator (low side) ~70 psi ~40°F (4°C) Refrigerant boils, absorbing heat from cabin air
Condenser (high side) ~250 psi ~115°F (46°C) Refrigerant condenses, releasing heat to outside air

The expansion valve is the dividing line between high and low pressure. It drops the pressure from ~250 psi to ~70 psi, which drops the boiling point from ~115°F to ~40°F, enabling the evaporator to absorb heat from 75°F cabin air.

2.4.2 — Why Refrigerants Boil at Low Temperatures

Refrigerants are chosen specifically because they have very low boiling points at atmospheric pressure — which means they are already vapour at room temperature unless placed under pressure. This allows the system to create a liquid that boils inside the evaporator at whatever low temperature the system needs.

Substance Boiling Point at 1 atm Typical Use
Water 212°F  (100°C) Not used as a refrigerant (boiling point too high)
Ammonia (R-717) −28°F  (−33°C) Industrial refrigeration, food processing
R-134a −15°F  (−26°C) Automotive AC, small appliances
R-410A −60°F  (−51°C) Residential and light commercial AC
R-32 −52°F  (−52°C) Modern residential systems (lower GWP)
📌
Why Water Doesn’t Work as a Refrigerant

Water’s boiling point of 212°F at atmospheric pressure means it would need to operate under a deep vacuum to boil at useful cooling temperatures. System pressures would be dangerously low (below atmospheric), making the equipment impractical and difficult to seal against air infiltration. Refrigerants with naturally low boiling points operate at above atmospheric pressure throughout the system, making leaks easier to detect (gas escapes rather than air entering).

2.4.3 — Superheat

Superheat is the condition where a vapour has been heated above its saturation temperature at a given pressure. A superheated vapour contains no liquid droplets — it is fully in the gas phase, just warmer than it needs to be to stay that way.

🔺

How to Measure Superheat

Superheat = Actual vapour temperature − Saturation temperature at that pressure.

Example: Evaporator pressure = 70 psi → saturation temp = 40°F. Suction line temp = 50°F.
Superheat = 50 − 40 = 10°F

🛡️

Why Superheat Is Required

The compressor is designed to compress vapour only. Liquid refrigerant cannot be compressed — it causes mechanical damage known as slugging.

A small amount of superheat (typically 8–12°F / 4–7°C) at the evaporator outlet ensures the refrigerant is completely vapour before entering the compressor.

🔬

What Superheat Tells a Technician

  • Low superheat (below 5°F) — liquid refrigerant may be reaching the compressor. Risk of slugging. System may be overcharged or expansion device is open too wide.
  • High superheat (above 15–20°F) — the evaporator is not fully used; system is undercharged or expansion device is too restrictive. Reduced cooling capacity.
  • Target superheat — typically 8–12°F for fixed-orifice systems; set at the expansion valve for TXV systems. Always refer to the manufacturer’s specifications.

2.4.4 — Subcooling

Subcooling is the condition where a liquid has been cooled below its saturation temperature at a given pressure. A subcooled liquid contains no vapour bubbles — it is fully in the liquid phase, just cooler than required for it to remain so.

🔻

How to Measure Subcooling

Subcooling = Saturation temperature at condenser pressure − Actual liquid temperature.

Example: Condenser pressure = 250 psi → saturation temp = 115°F. Liquid line temp = 100°F.
Subcooling = 115 − 100 = 15°F

Why Subcooling Matters

Subcooling ensures the refrigerant arrives at the expansion device as 100% liquid with no vapour bubbles (flash gas).

Flash gas in the expansion device causes erratic metering and reduces system capacity. Subcooling prevents this and adds useful cooling capacity. Typical target: 10–15°F (6–8°C).

🔧

Superheat & Subcooling Together — The Full Picture

Every refrigeration system has both superheat and subcooling occurring simultaneously. Together they bookend the phase-change regions of the cycle:

  • Subcooling ensures solid liquid enters the expansion device. Occurs at the end of the condenser and in the liquid line.
  • Expansion drops pressure and temperature; some liquid flashes to vapour (this is normal and unavoidable).
  • Evaporator boils the remaining liquid, absorbing latent heat from the building. This is where useful cooling happens.
  • Superheat at the evaporator outlet ensures all liquid is gone before the vapour enters the compressor.
📌
Connecting Back to Section 2

Superheat is a sensible-heat region (temperature rising, no phase change). Subcooling is also a sensible-heat region. The large middle zones — condensing and evaporating — are the latent-heat regions where the enormous energy exchanges that make refrigeration work are happening.

Test Your Knowledge
↑ Top