Unit 4 — Electrical Fundamentals
Section 1 — Introduction to Electricity

1.1 — Electrical Quantities

Before you can read a wiring diagram, measure a circuit, or diagnose an electrical fault, you need a precise vocabulary. This lesson establishes the core terms, quantities, units, and symbols that appear throughout every electrical job in 313A/313D work.

Jump to

1.1.1 — Core Electrical Terms

A refrigeration and air conditioning mechanic must be fluent in common electrical terminology to read documentation, communicate with other trades, and troubleshoot systems. The seven foundational quantities below appear on every equipment nameplate, wiring diagram, and test instrument you will use.

⚛️

Electric Charge

A property of matter that causes electrical effects. Electrons carry a negative charge; protons carry a positive charge. The movement of charge constitutes electric current.

⚡

Voltage (Potential Difference)

The electrical “pressure” that pushes electrons through a circuit. Measured in volts (V). HVAC/R systems use 24 V (control), 120 V, 208 V, 240 V, 277 V, or 600 V depending on the load and jurisdiction.

〰️

Current

The rate of flow of electric charge. Measured in amperes (A). Motor nameplates state full-load amps (FLA) and locked-rotor amps (LRA), which are critical for sizing conductors and protection devices.

🌀

Resistance

The opposition to current flow. Measured in ohms (Ω). All conductors, loads, and wiring introduce resistance that converts electrical energy into heat or other useful energy forms.

💡

Power

The rate at which electrical energy is consumed or converted. Measured in watts (W). Power determines equipment efficiency, circuit loading, and conductor sizing requirements.

🔁

Impedance

Total opposition to AC current, combining resistance and reactance. Measured in ohms (Ω). Relevant when working with inductive loads such as motors and transformers, which store and release energy in their magnetic fields.

📡

Frequency

The number of AC cycles per second. Measured in hertz (Hz). Canadian utility power is 60 Hz. Equipment, controls, and variable-frequency drives must be matched to system frequency.

1.1.2 — Circuit & Component Terms

Beyond the basic quantities, every HVAC/R technician must understand the names and roles of the components that make up a circuit. These terms appear daily on wiring diagrams, service manuals, and equipment specifications.

🔋

Source

Any device that supplies electrical energy: a utility service, a transformer secondary, or a control transformer. The source establishes the voltage that drives current through the circuit.

💡

Load

Any device that consumes electrical energy and converts it to another form: a motor, heater, solenoid valve, electronic control board, or light. The load is what the circuit is designed to power.

🔗

Conductor

A material that allows current flow with low resistance — copper and aluminium in building wiring. Conductors are sized by ampacity: the maximum continuous current they can carry safely.

🛡️

Insulator

A material that resists current flow: PVC, rubber, glass. Insulators separate live conductors from each other, from equipment enclosures, and from people, preventing shock and short circuits.

🎚️

Switch

Opens or closes a circuit to control current flow — manually (disconnect, toggle) or automatically (thermostat, pressure switch, float switch, flow switch). Every control circuit is built from a series of switches.

🎛️

Relay / Contactor

An electrically operated switch: a coil (electromagnet) pulls in contacts to control one or more circuits. Contactors switch high-power loads (compressors, fan motors); relays switch lower-power control circuits.

🔒

Overload / Over-Current Device

A protective device — fuse, circuit breaker, or thermal overload relay — that interrupts current when it exceeds a safe level, protecting conductors and equipment from heat damage.

🔁

Transformer

Transfers electrical energy between circuits by electromagnetic induction, stepping voltage up or down. In HVAC/R: steps 120 V or 208/240 V down to 24 VAC for thermostats and contactor coils.

1.1.3 — Alternating Current & Direct Current in HVAC/R

Electron Flow vs. Conventional Current

In metallic conductors, current is carried by electrons moving from regions of negative potential to positive potential. However, electrical diagrams and calculations use conventional current, defined as flowing from positive to negative — the opposite direction. For practical HVAC/R work you will draw and read schematics using conventional current. Understanding actual electron movement is useful conceptually but does not change how circuits are wired or measured.

Direct Current (DC)
  • Constant polarity and magnitude of voltage
  • Current flows continuously in one direction
  • Requires correct polarity connection
  • Used in: electronic control boards, VFDs (internal bus), ECMs, rectified low-voltage supplies
  • Semiconductor components depend on correct polarity — always follow manufacturer wiring diagrams
Alternating Current (AC)
  • Voltage periodically reverses polarity in a sinusoidal waveform
  • 60 Hz in Canada — 60 complete cycles per second
  • No polarity concern for most resistive and motor loads
  • Used in: compressors, fan motors, heaters, large solenoid valves
  • 24 VAC control circuits produced by control transformers for thermostats and contactor coils
Single-Phase AC
  • One alternating voltage; two current-carrying conductors plus equipment ground
  • Common in residential and light-commercial HVAC/R
  • Typical voltages: 120 V / 240 V split-phase; 208 V from three-phase panel
  • Motor starting requires a run capacitor (and often a start capacitor) to create the phase shift needed for rotation
Three-Phase AC
  • Three voltages equal in magnitude, 120° apart in phase
  • Standard for commercial and industrial compressors and large fan motors
  • Typical voltages: 208 V / 460 V / 575 V
  • Self-starting — no run capacitor required; phase rotation must be verified to prevent reverse rotation
💡
AC behaviour in inductive circuits

Motors and transformers are inductive loads. At start-up they draw inrush current (up to 6–8× FLA for compressors) before reaching steady state. Inductive loads also introduce a power factor lag between voltage and current, meaning the apparent power (kVA) is higher than the true power (kW). Both effects must be considered when sizing conductors, protection devices, and transformers.

1.1.4 — Ohm’s Law & Electrical Power

Three relationships govern almost every electrical calculation a field technician needs to make: Ohm’s Law links voltage, current, and resistance; the power formula adds watts; and the two combined cover every unknown on a nameplate or circuit.

Ohm’s Law

Ohm’s Law — Three Forms

V = I × R     I = V ÷ R     R = V ÷ I

V = voltage (volts)  |  I = current (amperes)  |  R = resistance (ohms Ω)

Knowing any two of the three quantities allows you to calculate the third. This is used constantly when:

🔧

Worked Example — Defrost Heater Current

A defrost heater element is rated at 240 V. Measured resistance of the element: 48 Ω.

I = V ÷ R = 240 ÷ 48 = 5 A

The technician clamps the heater circuit and reads 5.1 A — within normal tolerance. A reading of 0 A would indicate an open element; a reading significantly above 5 A would indicate a partial short or incorrect supply voltage.

Electrical Power

Power Formula — Three Forms

P = V × I     P = I² × R     P = V² ÷ R

P = power (watts W)  |  V = voltage (V)  |  I = current (A)  |  R = resistance (Ω)

These relationships are used to:

🔧

Worked Example — Sizing for a 3 kW Electric Heater

An electric strip heater is rated at 3 kW (3 000 W) at 240 V. What current does it draw, and what is the minimum circuit breaker size?

I = P ÷ V = 3 000 ÷ 240 = 12.5 A

The Canadian Electrical Code requires the overcurrent device for a continuous electric heater load to be sized at 125 % of the load current:

12.5 × 1.25 = 15.6 A → use a 20 A breaker (next standard size up)

The conductor must also be rated for at least 15.6 A continuous — a 12 AWG copper conductor (rated 20 A at 60 °C) is the typical selection.

💡
The Ohm’s Law / Power Triangle

Cover the quantity you want to find; the remaining two show the operation. For the V–I–R triangle: cover V → I×R; cover I → V÷R; cover R → V÷I. For the P–V–I triangle: cover P → V×I; cover V → P÷I; cover I → P÷V. These two triangles cover every basic electrical calculation needed in 313A/313D field work.

1.1.5 — Units of Measurement & Schematic Symbols

SI Units Used in HVAC/R Electrical Work

Quantity Unit Name Symbol Common Multipliers in HVAC/R
Voltage Volt V mV (millivolt, sensor signals); kV (kilovolt, utility transmission)
Current Ampere A mA (milliamp, electronic control signals); kA (fault current calculations)
Resistance Ohm Ω kΩ (kilohm, insulation resistance checks); MΩ (megohm, megger tests)
Power Watt W kW (kilowatt, motor and heater ratings); MW (megawatt, large plant)
Frequency Hertz Hz 60 Hz standard in Canada; VFDs output 0–120 Hz typical range
Energy Watt-hour Wh / kWh kWh on electricity bills; MWh for large facilities; BTU conversion: 1 kWh = 3 412 BTU
Capacitance Farad F µF (microfarad) for run and start capacitors; rated ±6 % (run) or ±20 % (start)

Common Schematic Symbols

Electrical diagrams use standardised symbols to represent devices and connections. Minor variations exist between standards (IEC, NEMA, Canadian Standards), but the symbols below are consistent across most HVAC/R equipment documentation.

Device Symbol Description Notes
Conductor (wire) Solid line Crossing wires with a dot = connected; crossing without a dot = not connected
Normally open (NO) contact Two parallel lines with a gap between them Open at rest; closes when the coil or actuator energises
Normally closed (NC) contact Two parallel lines connected by a diagonal line Closed at rest; opens when the coil or actuator energises
Relay / contactor coil Circle or rectangle labelled with the device designation When the coil is energised, all associated contacts change state simultaneously
Transformer Two coils facing each other, often with core lines between them Primary coil on left; secondary on right. Voltage ratio = turns ratio
Motor Circle with the letter M inside Three terminals shown for three-phase; two for single-phase
Fuse Rectangle or S-curve in the line Interrupts the circuit irreversibly on overcurrent; must be replaced after operation
Circuit breaker Rectangle with a dot and arc Interrupts and can be reset; provides both overcurrent and short-circuit protection
Ground (earth) Three horizontal lines decreasing in length downward Equipment grounding conductor (green/green-yellow) connects metallic enclosures to ground
⚠️
Diagram literacy is a core skill

A technician who cannot read and trace a wiring diagram is limited to replacing parts at random. Section 1.4 (Electrical Wiring Diagrams) builds directly on these symbols and teaches systematic circuit-tracing technique. Keep this symbol table as a reference as you work through the section.

Test Your Knowledge